HomePortfolioWorkers Building Chilled Water Fan Coil System Design, Abu Dhabi
HVAC Engineering

Workers Building Chilled Water Fan Coil System Design, Abu Dhabi

Abu Dhabi, UAE

Case Summary

Full HAP cooling and heating load analysis and 2-pipe fan coil system sizing for a G+3, 7,212 m² workers accommodation building housing 832 occupants in Abu Dhabi's extreme summer climate. 651.4 kW coil load.

Client Confidentiality

Due to client NDA commitments, the showcased projects represent only a portion of our work and not the full scope of what we've delivered.

Workers Building Chilled Water Fan Coil System Design, Abu Dhabi

A large workers' accommodation building in Abu Dhabi, ground plus three floors, 7,212 m², 832 occupants, required full cooling and heating load analysis and fan coil system sizing. The building faces Abu Dhabi's extreme summer climate, with peak outdoor air at 42.4°C DB / 22.7°C WB, combined with a high internal gains profile from lighting, equipment, and dense occupancy.

Our Approach: Floor-by-Floor HAP Analysis on a 2-Pipe Fan Coil System

  • Carrier HAP analysis using a 2-Pipe Fan Coil (2P-FC) terminal unit system
  • Four-floor model, ground to third, each floor 1,803 m² with 208 occupants
  • Individual space peak loads identified per floor; October 14:00 governs peak zone cooling, September 14:00 governs coil load
  • Ventilation outdoor air per ASHRAE 62.1: 2.5 L/s per person plus 0.30 L/s per m², totalling 4,244 L/s

Key Results

  • Peak sensible zone load: 474.0 kW (October 14:00)
  • Total coil load: 651.4 kW, with 554.4 kW coil sensible (September 14:00)
  • Supply airflow: 42,579 L/s
  • Winter heating load: 105.2 kW
  • Chilled water flow: 28.06 L/s at a 5.6°C temperature rise

Load Components That Drove the Design

The September coil peak breaks down into wall transmission (58,810 W across a 1,994 m² envelope), roof transmission (59,399 W), window solar and transmission gains, 83,033 W of overhead lighting, 86,540 W of electric equipment, occupant gains of 71,967 W sensible plus 110,906 W latent from 832 people, and ventilation gains of 91,498 W sensible plus 96,788 W latent. Coil entering conditions of 26.3°C DB / 19.2°C WB and leaving conditions of 15.4°C DB / 14.8°C WB closed out the psychrometric selection. The result is a fan coil system sized on documented physics rather than rules of thumb, in a climate that punishes undersized plant.

Ready to Start Your Project?

Let's Build Something Great Together.

Partner with Fluxiss for engineering that holds up - under pressure, under load, under scrutiny.