Antenna Support Structure Wind Load Analysis and AISC 360-16 Code Check
Amarillo, Texas, USA
MIDAS/Civil analysis of a two-antenna steel mount in Amarillo, Texas, for 108 mph wind: maximum stress ratio 0.336 and deflection 0.318 in.
Challenge
A steel structure carrying two 35 lb antennas with 1 ft eccentricity needed design and code checking for a 108 mph basic wind speed (Risk Category II).
Approach
The structure was modelled in MIDAS/Civil with wind pressure to ASCE 7-16 (qz = 22.84 psf). Angle, double-angle and HSS members in ASTM SS304 were checked to AISC 360-16 ASD under three load combinations, together with the bolt connection.
Result
The maximum stress ratio was 0.336, deflection 0.318 in against a 0.6 in limit, and bolt shear capacity 8,836 lb against a 39 lb demand.
Scope of Work
- Wind load derivation
- Member design and code check
- Deflection check
- Bolt shear check
Deliverables
- Structural analysis report
Similar projects

Refinery Steel Structure Design and Vetting: Gantry, Flare Stack Anchors and Waste Heat Recovery Boiler
Structural vetting and design at Pakistan Refinery Ltd. (PRL): JP-1 gantry, flare stack anchor bolts, a waste heat recovery boiler structure and more.

Steel Structures for a 65 KLPD Ethanol Fermentation and Distillation Plant
Design and detailed engineering of fermentation and distillation steel structures and civil foundations for a 65 KLPD ENA ethanol plant at Chashma.

Structural Analysis of a Power Plant Main Boiler Stack
Static and dynamic structural analysis of the main boiler stack at Saba Power Plant, Farooqabad, to AISC, with stress analysis of the stack piping.
Let's Build Something Great Together.
Partner with Fluxiss for engineering that holds up - under pressure, under load, under scrutiny.