Cooling and Heating Load Analysis for a University Building with a Glass Dome

Cooling and Heating Load Analysis for a University Building with a Glass Dome

Edwardsville, Illinois, USA

Project Lead
Syed Nasir
Lead Consultant, Founder & CEO, Fluxiss
Discuss a similar project

Space-by-space Carrier HAP loads for 14 zones at SIUE, including an equivalent-volume glass dome model: 180,179 Btu/hr cooling, 8,500 CFM.

Challenge

The Center for Spirituality & Sustainability at Southern Illinois University Edwardsville (SIUE) has a central hall capped by a glass dome, a shape HAP's rectangular room model cannot represent directly. The building is served by campus chilled water. Fluxiss carried out this work as engineering subcontractor.

Approach

The dome's effective volume was calculated with spherical cap geometry (3,283 ft³) and converted to an equivalent 15 ft cube, with walls modelled as acrylic glazing and the roof as a skylight. Its load was added to the central hall zone, and all 14 zones were analysed.

Result

Total loads were 180,179 Btu/hr cooling and 156,248 Btu/hr heating at 8,500 CFM. The dome alone was 51,515 Btu/hr cooling and 2,674 CFM, and heating loads were documented for sizing the campus CHW connection.

Scope of Work

  • Glass dome equivalent volume modelling
  • 14-zone load analysis
  • Campus CHW connection loads

Deliverables

  • Zone-by-zone load report

Codes & Tools

ASHRAECarrier HAP v4.90