Chilled Water Fan Coil System Design for a 832-Occupant Workers Building in Abu Dhabi

Chilled Water Fan Coil System Design for a 832-Occupant Workers Building in Abu Dhabi

Abu Dhabi, UAE

Project Lead
Syed Nasir
Lead Consultant, Founder & CEO, Fluxiss
Discuss a similar project

Carrier HAP load analysis and 2-pipe fan coil sizing for a 7,212 m² G+3 workers building in Abu Dhabi: 651.4 kW coil load, 28.06 L/s chilled water.

Challenge

A G+3 workers' accommodation building of 7,212 m² with 832 occupants faced Abu Dhabi summer peaks of 42.4°C DB, with high internal gains from lighting, equipment and occupancy.

Approach

A four-floor 2-pipe fan coil model was built in Carrier HAP with individual space peaks per floor. Ventilation was set at 2.5 L/s per person plus 0.30 L/s·m² to ASHRAE 62.1, giving 4,244 L/s of outdoor air.

Result

Total coil load was 651.4 kW (September 14:00), peak zone sensible load 474.0 kW, supply airflow 42,579 L/s, heating load 105.2 kW and chilled water flow 28.06 L/s at 5.6°C ΔT.

Scope of Work

  • Space-by-space cooling and heating loads
  • Ventilation sizing
  • Fan coil and CHW sizing

Deliverables

  • HAP load report
  • Design load breakdown

Codes & Tools

ASHRAE 62.1Carrier HAP v4.90