Seismic Pipe Stress Analysis of a Data Centre Drainage Riser and Level Pipework

Seismic Pipe Stress Analysis of a Data Centre Drainage Riser and Level Pipework

Frankfurt, Germany

Project Lead
Syed Nasir
Lead Consultant, Founder & CEO, Fluxiss
Discipline Lead
Mr. Wassam
Piping Engineer, Fluxiss
Discuss a similar project

BS EN 13480-3 stress analysis of a Frankfurt data centre drainage riser in Seismic Zone 4, with peak stress at 9.1% of allowable.

Challenge

A Frankfurt data centre needed its drainage riser and typical level pipework (OD 168.3 mm) analysed for Seismic Zone 4, soil category C, Rp = 3.5 and I = 1.4.

Approach

Sustained, expansion and hydrotest cases were run in CAESAR II to BS EN 13480-3. The riser was anchored 12 m from its base with vertical clips at several elevations, and level pipework used guides or bracing every 6 m, seismic lateral restraint and rigid hangers.

Result

Maximum stresses were 7.71 MPa sustained (5.1% of allowable), 30.05 MPa expansion (9.1%) and 8.52 MPa hydrotest (3.8%). A DXF file of all support locations was supplied to the contractor.

Scope of Work

  • Riser anchor and clip strategy
  • Level pipework guide and hanger strategy
  • Seismic lateral restraint

Deliverables

  • Stress analysis report
  • Support load tables
  • DXF support location file

Codes & Tools

BS EN 13480-3CAESAR II