Seismic Pipe Stress Analysis of a Data Centre Drainage Riser and Level Pipework
Frankfurt, Germany
BS EN 13480-3 stress analysis of a Frankfurt data centre drainage riser in Seismic Zone 4, with peak stress at 9.1% of allowable.
Challenge
A Frankfurt data centre needed its drainage riser and typical level pipework (OD 168.3 mm) analysed for Seismic Zone 4, soil category C, Rp = 3.5 and I = 1.4.
Approach
Sustained, expansion and hydrotest cases were run in CAESAR II to BS EN 13480-3. The riser was anchored 12 m from its base with vertical clips at several elevations, and level pipework used guides or bracing every 6 m, seismic lateral restraint and rigid hangers.
Result
Maximum stresses were 7.71 MPa sustained (5.1% of allowable), 30.05 MPa expansion (9.1%) and 8.52 MPa hydrotest (3.8%). A DXF file of all support locations was supplied to the contractor.
Scope of Work
- Riser anchor and clip strategy
- Level pipework guide and hanger strategy
- Seismic lateral restraint
Deliverables
- Stress analysis report
- Support load tables
- DXF support location file
Similar projects

Seismic Pipe Stress and API-617 Compressor Nozzle Assessment for a Refinery Upgrading Project
Seismic and static analysis of a 6-inch refinery line where one added support brought compressor nozzle loads from fail to pass under API-617.

Chilled Water Pipe Stress Analysis up to DN1000 for Microsoft MS-LON1
Lead pipe stress analysis, as subcontractor, of CHW piping up to DN1000 for Microsoft MS-LON1, with a friction factor study for product selection.

Antenna Support Structure Wind Load Analysis and AISC 360-16 Code Check
MIDAS/Civil analysis of a two-antenna steel mount in Amarillo, Texas, for 108 mph wind: maximum stress ratio 0.336 and deflection 0.318 in.
Let's Build Something Great Together.
Partner with Fluxiss for engineering that holds up - under pressure, under load, under scrutiny.