Multi-User Horizontal Lifeline Design for a Tank Lorry Loading Facility

Multi-User Horizontal Lifeline Design for a Tank Lorry Loading Facility

Pakistan

Project Lead
Syed Nasir
Lead Consultant, Founder & CEO, Fluxiss
Discuss a similar project

Single- and two-user horizontal lifeline analysis to CSA Z259.16 for a 16.8 m span over a tank lorry platform, with 80.3 kN governing anchorage load.

Challenge

Operators on a 10 ft tank lorry platform needed fall protection, and the lifeline had to be checked for both one and two users on the same span.

Approach

A 16.8 m span, 12 mm rope lifeline was analysed to CSA Z259.16 for a single user and for two users using a lumping factor of 1.75 (175 kg effective weight).

Result

For one user, cable tension at arrest was 30.53 kN and required clearance 2.479 m, below the 3.048 m lorry height. The two-user case gave 46.0 kN cable tension and an anchorage design load of 80.3 kN, which governed the design.

Scope of Work

  • Single-user scenario
  • Two-user scenario with lumping factor
  • Fall clearance check
  • Anchorage design load

Deliverables

  • HLL design calculation report

Codes & Tools

CSA Z259.16Energy Balance Method calculations